Chilled water issues

A cooling water closed loop is installed in the production plant

The cooling water is used for cooling different parts of the equipment that is used in the plant.

There are two main parameters of the water: pH and conductivity. Both parameters are controlled and should be kept within certain limits.

Typically the pH of the water slightly decreases. This is compensated by adding a small amount of NaOH.

Suddenly pH started to reduce faster than usual. The compensation requested much more amount of NaOH which may result in a strong increase in the conductivity.


A regular audit showed that some flanges are affected by strong corrosion as shown below:




Login to comment

Similar projects

In past decades, polymeric micropillar devices have gained a great deal of attention in micro and nano technology research as the result of their potential and practical usage in many applications. This project is going to deal with the process of how to fabricate the magnetic micropillars, from the beginning – the planning and design, improving the existing process, lithography to create the base silicon mold and then creating the PDMS pillars that contains nano magnetic particles of Fe_3 O_4, the process today is not efficient enough in terms of cost and time and we are wishing to improve it, in the end we will have a device with micro-pillars that can move correspondingly to external magnetic field which will help us to do many advanced experiments in the biology field like using the device for cell stimulation.

Mark Reitman avatar
Mark Reitman

The aim of the project is to evaluate the amount of removed corrosion on a cold-rolled steel 1008 specimen after the use of a rust remover.

maisamn0304 avatar
maisamn0304